Impulse voltage and current test systems

Impulse test systems are used for impulse testing of high voltage devices such as transformers, cables, gas-insulated switchgears (GIS), arresters, etc. The test systems generate lightning impulse voltage waveform (LI, 1.2/50 µs), chopped lightning impulse voltages waveform (LIC, front, crest or tail chopped), and switching impulse voltage (SI, 250/2500 µs) in accordance with IEC 60060-1; as well as IEC 60076-3 for transformers, and IEC 62067, 60840 und 60502-1 for cables).
Impulse test systems are available in different configurations boardly divided in two types.
1. W series: 100kV, 5/10 KJ per stage with max. rating up to 1600 kV, 160 kJ
2. V series: 200 kV, 20/30 KJ per stage with max. rating of 6000 kV, 900 kJ
The standard test system consists of following components:
- Impulse Generator
- HVDC Charging Power Supply
- Impulse Voltage Divider
- Impulse Control, Measuring and Analyzing System
Optional Acessories:
- Impulse Current Shunts
- Multi-stage Chopping Gap
- Overshoot Compensation Device
- Glaninger Circuit
- Recurrent Impulse Generator
- Reference Impulse Calibrator
APPLICATION
Applications cover testing according to IEC, ANSI/IEEE as well as other national & international standards. The Impulse Voltage System can be used to test any high voltage electrical equipment like:
- Power & Distribution Transformers
- Cables
- Surge / Lightning Arresters
- Insulators
- Instrument Transformers
- Bushings
- GIS
- Switchgears
- Shunt Reactors
- Special Application Transformers
FEATURES:
- Low internal inductance ensures high efficiency.
- Easy & quick reconfiguration to meet different testing requirements.
- User friendly operation through computer-controlled hardware.
- Special resistors, capacitors and inductors can be supplied for other impulse shapes like (8/20 μS, 4/10 μS) as per IEC 60099 and/or other load testing.
- Reliable, accurate and fail – safe triggering circuitry.
- Load range can be extended using Glaninger Circuit, overshoot compensation, termination resistors and special wave shaping resistors.
- The electronic measurement and controlling device include optical isolators to provide safety of the electronics in high voltage environment thus ensuring trouble-free operation.
Enquire Now